REES 04945-800, Cable/Rope Operated Switch    ree rees electrical controls logo

REES 04945-800,  Rope Operated Sequence Switch

 Back to Store  / REES

Features/Applications

The following “slack cable” style switch has 1 NO and 1 NC “Make-Before-Break” contacts for use in normal start-stop applications. This switch does NOT latch in any position and should only be used for non-emergency applications.

The action of this switch is that when the switch actuating arm is pulled by a cable the switch contacts will change state, the NO will be closed and the NC will go open. When the force on the cable is removed from the actuator arm, spring pressure will return it to its normal position, while the contacts are held in position through a ratchet mechanism. The next time the cable is pulled, the action is repeated and the contacts return to their original state.

The housing and cover are made from a glass filled black polycarbonate. The mounting base and double end actuator arm are die cast from a high strength zinc alloy powder coat painted white.

Each captive terminal on the replaceable contact block will accept (2) #14 AWG stranded wires.

  • Unique “Pull-On”, “Pull-Off” function
  • Gold plated contacts eliminate high resistance tarnishing
  • External steel components are made from #303 stainless
  • Nema 4X (indoor), IP 66                                                                      

There are two ½ “NPT conduit openings. The maximum cable recommended cable length is 200 feet with a maximum interval support of 10 feet.

The mechanical life of the switch is in excess of 150,000 mechanical and 1,000,000 electrical operations.

This type of device can be found on various conveyor installations as well as other stations that require the “pull-on”, “pull-off” function.

The rugged construction and long term reliability makes this cable pull switch well suited to function within various environments.

Not UL Listed or CSA Certified. CE Compliant

Electrical Ratings

“HEAVY DUTY – A600 / N150”
CE Compliant IEC/EN 60947-5-1

Environmental Temperature Range

Operating: +32oF to +131oF (0oC to +55oC)
Storage: -40oF to +185oF (-40oC to +85oC)

Note: Operating temperatures at 0oC are based on the absence of freezing moisture and liquids.

 

Normal Potential Normal Current Inrush Current
110-120 acvolts 6.0 amp. 60.0 amp.
220-240 aca 3.0 amp. 30.0 amp.
440-480 aca 1.5 amp. 15.0 amp.
550-600 aca 1.2 amp. 12.0 amp.
115-125 dcb 2.2 amp. -----

 Power factor 0.35 or less

 Inductive loads as specified in Section 125 of Industrial

   Control Devices, Controllers and Assemblies, ANSI /

   NEMA ICS 2-1988

 

Specifications  

Trip Force

10 lb

Operating Force Between 10 ft. Supports

1.2 lb

Reset Type

Manual

Contact Arrangement

NO + NC
(make-before-break)