E90S UC MINI DC BREAKERS

e90suc
Part # E91SUCB06 Base price: $22.10 Configured Price: $22.10
Choose Number of Poles
Choose Trip
Choose Amps

5 items in stock
in stock
+ Add to cart

Features

STANDARDS / APPROVALS

  • CE
  • VDE0641
  • IEC60898-2

TECHNICAL DATA

  • 0.5 Amp - 63 mp (C trip)
  • Short circuit capacity (6kA) IC
  • 6 Amp - 63 Amp (B trip)
  • Screw torque to 4.5Nm
  • Mechanical endurance (20,000 operations)
  • Electrical endurance (10,000 operations)
  • Current limiting design
    (Energy limit class 3)
  • Max. DC Volts (1P)220VDC
                        (2P)440VDC
  • Min. DC Volts 12V
  • Shock resistance (in x, y, z direction)
    20g with shock duration of 10ms
    (minimum 18 shocks)
    40g with shock duration of 5ms
    (minimum 18 shocks)
  • Vibration resistance (in x, y, z direction)
    3g in frequency range 10 to 55Hz
    (operating time at least 30 minutes)
    according to IEC 77 16.3 and DIN 40046 part 8
  • Storage temperature
    From -55°C up to +55°C
    according to IEC 88 part 2-1
  • Tropicalized to +55°C / 95% RH
    (Acc. IEC60058-2 / DIN 40046
  • NOTE: must observe polarity markings due to
              permanent magnet in the MCB

TECHNICAL PERFORMANCE

OPERATIONAL TRIP CHARACTERISTICS

  • B = 3-5 x magnetic release
  • C = 5-10 x magnetic release